EPA 608 numbers to memorize
Updated: · Checked: 2026-11-21
The key EPA 608 numbers are: 25 questions per section, 70% to pass (84% mail-in Type I), fill cylinders no more than 80%, leak rates of 20% commercial, 30% industrial and 10% comfort cooling, 50 lb for ODS leak repair vs 15 lb for HFC (from 2026), 5 lb small appliances, add 14.7 for psia, heat oil to 130°F (Type III), the 15 lb system-dependent limit, 3-year records, and the 82.156 evacuation table split at 200 lb and November 15, 1993.
This is a one-page study sheet. Every number below comes from the regulation (40 CFR Part 82 and Part 84) or EPA's own pages, checked on 2026-11-21. We left out numbers that show up in some study guides but that we could not confirm on an official page. Learn these first; they come up again and again on the Core, Type I, II and III sections.
The test itself
| Number | What it means | Source |
|---|---|---|
| 25 | Questions per section (Core, Type I, Type II, Type III) | Appendix D |
| 50 | Questions on a Type I, II or III test (25 Core + 25 type) | Appendix D |
| 100 | Questions on the Universal test (25 Core + 3 × 25) | Appendix D |
| 70% | Passing score, closed-book Type I, II, III and Universal | Appendix D |
| 84% | Passing score, mail-in Type I | Appendix D |
| 30 days | Program must give your results, and send your card, no later than 30 days from the test | Appendix D |
More on scoring: EPA 608 passing score.
Sizes and charges
| Number | What it means | Source |
|---|---|---|
| 5 lb | Small appliance = factory-sealed with five pounds or less of refrigerant (Type I) | 82.152 |
| 15 lb | System-dependent recovery equipment may not be used on appliances with a full charge of more than 15 pounds (unless permanently attached as a pump-out unit) | 82.156(e) |
| 200 lb | The split in the evacuation table: under 200 lb vs 200 lb or more | 82.156 Table 1 |
| 50 lb | ODS leak repair (CFC/HCFC, e.g. R-22) applies at a full charge of 50 lb or more | 82.157 |
| 15 lb | HFC leak repair (AIM Act, from Jan 1, 2026) applies at 15 lb or more, GWP above 53 | 84.106 |
The 2026 HFC rule is new. Details: What changed for HFC leak repair in 2026.
Leak rates (same three for ODS and HFC)
| Appliance type | Leak rate that triggers repair |
|---|---|
| Commercial refrigeration | 20% |
| Industrial process refrigeration | 30% |
| Comfort cooling and other appliances | 10% |
Repair within 30 days (120 days if an industrial process shutdown is needed). Sources: 82.157(c)(2), 84.106(c)(2).
Pressures, temperatures, percentages
| Number | What it means | Source |
|---|---|---|
| 14.7 | Add 14.7 to psig to get psia | EPA test topics (Type 2) |
| 80% | Don't fill cylinders more than 80 percent full | EPA test topics (Core) |
| 130°F | Type III: heat oil to 130°F before removing it, to release less refrigerant | EPA test topics (Type 3) |
| 104°F | Temperature used to define low, medium, high and very high pressure | 82.152 |
| 0 psig | Non-major repair: evacuate (medium/high/very high) or pressurize (low-pressure) to no higher than 0 psig before opening | 82.156(a)(1) |
| 5 psig | Oil changes: no higher than 5 psig before opening | 82.156(a)(1)(iii) |
Small appliances (Type I) recovery
| Recovery equipment | Requirement |
|---|---|
| Made before Nov 15, 1993 | Recover 80% of the refrigerant |
| Made on or after Nov 15, 1993, compressor working | Recover 90% |
| Made on or after Nov 15, 1993, compressor not working | Recover 80% |
| Either | Or evacuate to four inches of mercury vacuum |
Source: 82.156(b).
Required evacuation levels (Table 1 of 82.156)
As given in 40 CFR 82.156, in inches of Hg vacuum (relative to 29.9 inches of Hg), except where noted. It covers appliances other than small appliances, MVACs and MVAC-like appliances. EPA explains it in plain English on its service practice page.
| Type of appliance | Recovery equipment made or imported before Nov 15, 1993 (inches of Hg vacuum) | Recovery equipment made or imported on or after Nov 15, 1993 (inches of Hg vacuum) |
|---|---|---|
| Very high-pressure appliance | 0 | 0 |
| High-pressure appliance, or isolated component of such appliance, with a full charge of less than 200 pounds of refrigerant | 0 | 0 |
| High-pressure appliance, or isolated component of such appliance, with a full charge of 200 pounds or more of refrigerant | 4 | 10 |
| Medium-pressure appliance, or isolated component of such appliance, with a full charge of less than 200 pounds of refrigerant | 4 | 10 |
| Medium-pressure appliance, or isolated component of such appliance, with a full charge of 200 pounds or more of refrigerant | 4 | 15 |
| Low-pressure appliance | 25 mm Hg absolute | 25 mm Hg absolute |
Memory tips: November 15, 1993 is the date that splits old and new recovery machines. 200 lb splits small and large systems. Low-pressure is always 25 mm Hg absolute.
Records
| Number | What it means | Source |
|---|---|---|
| 3 years | The default for records: leak repair, refrigerant sales invoices, disposal records, and your own certificate copy (until 3 years after you stop working as a tech) | 82.161, 82.157 |
How to use this sheet
- Cover the right column and say each number out loud.
- Take a timed mock and see which numbers you miss.
- Go back to the section practice: Core, Type I, Type II, Type III.
Start with our free practice test. Ready608 is a prep site; you take the real test with an EPA-approved certifying organization.
Quick answers
What is the most important number on the EPA 608 test?
There is no single one, but the evacuation table in 82.156 has many numbers in one place: 0, 4, 10, 15 inches of Hg vacuum and 25 mm Hg absolute, split by 200 lb and November 15, 1993.
How full can a recovery cylinder be?
No more than 80 percent full. EPA lists the risks of filling cylinders more than 80 percent full as a Core test topic.
Why are there two leak-repair thresholds, 50 lb and 15 lb?
50 lb is for appliances with ODS refrigerant like R-22 under 40 CFR 82.157. Since January 1, 2026, 40 CFR 84.106 covers HFC and certain substitute appliances at 15 lb or more (GWP above 53).
Why did you leave some numbers out?
Some numbers in study guides are not stated on EPA's pages or in the regulation. We only list numbers we confirmed on an official source.
What to do next: See where you stand
Take the free 25-question EPA 608 sample test. No sign-up.
Take the free test →Sources
- eCFR: Appendix D to Subpart F of Part 82
- eCFR: 40 CFR 82.152 Definitions
- eCFR: 40 CFR 82.156 Proper evacuation of refrigerant from appliances
- eCFR: 40 CFR 82.157 Appliance maintenance and leak repair
- eCFR: 40 CFR 82.161 Technician certification
- eCFR: 40 CFR 84.106 Leak repair
- EPA: Section 608 Test Topics
- EPA: Stationary Refrigeration Service Practice Requirements
Checked: 2026-11-21. Ready608 is an independent study tool, not EPA or a certifying organization.