What changed for HFC leak repair in 2026? (AIM Act ER&R rule for technicians)

Updated: · Checked: 2026-11-21

Since January 1, 2026, 40 CFR 84.106 (AIM Act) requires leak repair for appliances with a full charge of 15 lb or more of an HFC or a substitute with GWP greater than 53, using the same 20% commercial, 30% industrial process and 10% comfort cooling/other leak rates, with repairs by a certified technician. Commercial and industrial systems with 1,500 lb or more need automatic leak detection; ODS appliances with 50 lb or more stay under 40 CFR 82.157.

Short answer: since January 1, 2026, leak repair rules cover HFC equipment, not only CFC/HCFC equipment. The new rule is 40 CFR 84.106, under the AIM Act. It applies to appliances with a full charge of 15 pounds or more of an HFC, or of a substitute with a global warming potential (GWP) greater than 53. The leak rates are the same ones you know: 20% commercial refrigeration, 30% industrial process refrigeration, 10% comfort cooling and other appliances. Repairs must be done by a certified technician. EPA's summary is its January 2026 fact sheet, AIM Act: Leak Repair Requirements for Appliances Containing HFCs and Certain Substitutes.

Old rule vs new rule

Section 608 rule (40 CFR 82.157)AIM Act rule (40 CFR 84.106)
RefrigerantClass I or class II (CFC, HCFC, e.g. R-22), or a blend containing themHFCs, and substitutes with GWP greater than 53
SizeFull charge of 50 lb or moreFull charge of 15 lb or more
StartIn place (applies to ODS only since April 10, 2020)January 1, 2026
Leak rates20% commercial / 30% industrial process / 10% comfort cooling and other20% commercial / 30% industrial process / 10% comfort cooling, refrigerated transport and other
Repair deadline30 days (120 with industrial process shutdown)30 days (120 with industrial process shutdown)
Chronic leakers50 lb+, 125% of full charge in a calendar year, report by March 115 lb+, 125% of full charge in a calendar year, report by March 1
RecordsAt least 3 yearsAt least 3 years

Sources: 40 CFR 82.157, 40 CFR 84.106.

Who is covered, and who is not

  • Covered: refrigerant-containing appliances with a full charge of 15 lb or more where the refrigerant is an HFC (a "regulated substance") or a substitute with GWP above 53.
  • Not covered by 84.106: appliances containing solely an ozone-depleting substance. Those stay under 40 CFR 82.157 (50 lb or more).
  • Not covered by 84.106: appliances "used for the residential and light commercial air conditioning and heat pump subsector."

EPA's fact sheet notes that 53 is the lowest AIM Act exchange value. The rule comes from the Emissions Reduction and Reclamation (ER&R) final rule published October 11, 2024 (89 FR 82682).

What a technician has to do

  1. Calculate the leak rate when you add refrigerant to a covered appliance.
  2. If it is over the rate (20/30/10%), the leak must be repaired within 30 days (120 if an industrial process shutdown is needed). Repairs must be done by a certified technician.
  3. Verification tests: an initial test within the repair window, and a follow-up within 10 days.
  4. Leak inspections after going over the rate: commercial or industrial process refrigeration with 500 lb or more, every three months; commercial or industrial process with 15 lb to less than 500 lb, once a year; comfort cooling and others, once a year.
  5. Keep records for at least 3 years.

Extensions are capped at 180 days (270 with an industrial process shutdown), and requests go to EPA electronically. Owners also had to determine the full charge of 15 lb+ appliances "By January 1, 2026, or upon installation." (84.106)

Automatic leak detection for 1,500 lb+ systems

Under 40 CFR 84.108, industrial process refrigeration or commercial refrigeration with a full charge of 1,500 pounds or more of an HFC or substitute with GWP above 53 needs automatic leak detection (ALD).

When the system was installedALD deadline
On or after January 1, 2026Upon installation, or within 30 days of installation
January 1, 2017 to before January 1, 2026By January 1, 2027

ALD must be audited and calibrated every year. Direct sensors must detect 10 ppm and alert at 100 ppm. Condition-monitoring systems alert at a loss of 50 lb or 10% of the full charge, whichever is less.

Proposed: transport refrigeration units (not final)

On May 21, 2026, EPA proposed to exempt all road and intermodal container transport refrigeration units (TRUs) from the leak repair requirements (EPA fact sheet, May 2026). This is a proposal only. As of the eCFR text dated November 19, 2026, refrigerated transport is still listed in 84.106 at the 10% rate. Don't treat the exemption as law until EPA finalizes it.

Other 2026 AIM Act dates techs hear about

  • From January 1, 2026, refrigerant sold as "reclaimed" can contain no more than 15% virgin HFC by weight (84.112).
  • From January 1, 2029, servicing HFC equipment in supermarket systems, refrigerated transport and automatic commercial ice makers must use reclaimed refrigerant (84.112).
  • From January 1, 2028, rules apply to disposable cylinders with an HFC heel (84.116).

Source: 40 CFR Part 84 Subpart C.

Is this on the EPA 608 test?

EPA's 608 leak repair web page still describes only ODS appliances with 50 lb or more (EPA leak repair page), and the test bank comes from EPA. Study the 608 numbers for the test, and know the 2026 HFC rule for the job. See EPA 608 numbers to memorize.

Not certified yet? You need Section 608 certification for this work. Compare Ready608 prep plans ($29 one type, $49 Universal, one-time; the real test fee is separate) and take the real test with an EPA-approved certifying organization.

Quick answers

Does the 2026 HFC leak rule apply to home AC systems?

No. 40 CFR 84.106 excludes appliances used for the residential and light commercial air conditioning and heat pump subsector.

Did the leak rates change?

No. The HFC rule uses the same 20% commercial, 30% industrial process and 10% comfort cooling/other rates. What changed is the refrigerant (HFCs and substitutes with GWP above 53) and the size (15 lb instead of 50 lb).

What about R-22 systems?

Appliances containing solely an ozone-depleting substance, like R-22, stay under the Section 608 leak repair rule, 40 CFR 82.157, which applies at 50 lb or more.

Are trailer and container refrigeration units exempt?

Not yet. EPA proposed an exemption for road and intermodal TRUs on May 21, 2026, but it is a proposal. The eCFR text as of November 19, 2026 still lists refrigerated transport at 10%.

Which systems need automatic leak detection?

Commercial refrigeration and industrial process refrigeration with a full charge of 1,500 lb or more of HFC or a substitute with GWP above 53. New systems from 2026: at installation or within 30 days; systems installed from 2017 through 2025: by January 1, 2027.

What to do next: Practice for your section